Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/15/2009

Applicant:

CHRISTOPHER FAMILY 2001 REVOC TR 50% &

Description:

Full Inspection conducted 12/15/09 I have received a copy of this report and understand the corrections needed: ________________ Business Representative: Andrew Papanikolas Phone: 747-7600 Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after) Certificate of Occupancy: NOT ON FILE & NOT POSTED Extinguishers Serviced and Tagged (09/09) - Occupant shall perform monthly inspections and indicate such on tag. Remember to keep extinguishers unobscured and unobstructed.

Outstanding Inspections

Case Number: T09FR03772
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/15/2009 INSP - FULL dgreenl1 Violation Please correct the following violations of the Tucson Fire code: TFC 2204.4.1 - Approved containers required. Class I, II and IIIA liquids shall not be dispensed into a portable container unless such container is of approved material and construction, and has a tight closure with screwed or spring-loaded cover so designed that the contents can be dispensed without spilling. Liquids shall not be dispensed into portable tanks or cargo tanks. _____ Replace portable plastic gas cans with UL or FM approved metal cans TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____Replace unapproved extension cord (North office) TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____Recharge fire extinguisher (south shop door) TFC 1008.1.8 - Door operations. … egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exceptions: In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____Replace double keyed deadbolt with thumb turn (South door) TFC 105.6.16 - Flammable and combustible liquids. An operational permit is required: 3. To store, handle or use Class II, Class IIIA or Class IIIB liquids in excess of 25 gallons in a building or in excess of 60 gallons outside a building... _____ Obtain permits for all above-ground storage tanks (AST)'s (Prior to permit inspection, tanks shall comply with NFPA 30, be equipped with pressure-relief and emergency vents and be labeled with contents… applicant shall provide a drawing showing location and contents of tanks) TFC 2703.4 - Material Safety Data Sheets. Material Safety Data Sheets (MSDS) shall be readily available on the premises for hazardous materials regulated by this chapter. When a hazardous substance is developed in a laboratory, available information shall be documented. Exception: Designated hazardous waste. _____ Provide MSDS and training. TFC 2703.5 - Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____ Post "Flammable" sign at entrance to room containing used oil tank. TFC 2703.7.1 - Smoking. Smoking shall be prohibited and "No Smoking" signs provided as follows: 1. In rooms or areas where hazardous materials are stored or dispensed or used in open systems in amounts requiring a permit in accordance with Section 2701.5. 2. Within 25 feet (7620 mm) of outdoor storage, dispensing or open use areas. 3. Facilities or areas within facilities that have been designated as totally "no smoking" shall have "No Smoking" signs placed at all entrances to the facility or area. Designated areas within such facilities where smoking is permitted either permanently or temporarily, shall be identified with signs designating that smoking is permitted in these areas only. 4. In rooms or areas where flammable or combustible hazardous materials are stored, dispensed or used. Signs required by this section shall be in English as a primary language or in symbols allowed by this code and shall comply with Section 310. _____ Post "NO SMOKING" signs at entrance to rooms where flammable and combustible liquids are used.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03772
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/30/2009 INSP - REINSPECTION dsgreenl1 Approved Tank permit pending All other items corrected