Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

12/14/2009

Applicant:

EL DORADO HOSPITAL

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T09FR03764
Case Description: INSPECTION
Total Completed Inspections - 13
End Date Description Inspector Results Comments
12/14/2009 INSP - FULL RSPANGLE Approved NOTE: F/A AND SPRINKLER SYSTEM ANNUAL INSP. REPORTS WERE SUBMITTED AT TIME OF INSP. 5 YEAR CHECK VALVE INSP. IS DUE. FIRE DRILL RECORDS ARE IN COMPLIANCE.
12/14/2009 INSP - FULL RSPANGLE Approved 12.) TFC 906.2 PORTABLE FIRE EXTINGUISHER IN 1ST FLOOR MAIN ELECTRICAL ROOM IS PAST DUE FOR ANNUAL INSPECTION.
12/14/2009 INSP - FULL RSPANGLE Approved 11.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN 1ST FLOOR I.T. ROOM OF SENIOR SERVICES.
12/14/2009 INSP - FULL RSPANGLE Approved 10.) TFC 703.1.1 SEAL WALL PENETRATION ABOVE CEILING TILE GRID IN RESPIRATORY THERAPY 1ST FLOOR OFFICE.
12/14/2009 INSP - FULL RSPANGLE Approved 9.) TFC 703.1.1 REPLACE MISSING CEILING TILE & ESCUTCHEON IN CARDIAC REHAB I.T. CLOSET.
12/14/2009 INSP - FULL RSPANGLE Approved 8.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN 1ST FLOOR HALLWATY NEAR I.T. ROOM.
12/14/2009 INSP - FULL RSPANGLE Approved 7.) TFC 703.1.1 IN I.T. ROOM 1ST FLOOR URGENT CARE SEAL AROUND CABLES RUNNING THROUGH CONDUIT.
12/14/2009 INSP - FULL RSPANGLE Approved 6.) TFC 703.1.1 REPLACE MISSING CEILING TILE ON 1ST FLOOR BY OLD BREAK ROOM.
12/14/2009 INSP - FULL RSPANGLE Approved 5.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN MAIN HALLWAY BY CARDIAC REHAB.1ST FLOOR.
12/14/2009 INSP - FULL RSPANGLE Approved 4.) TFC 703.1.1 SEAL AROUND ELECTRICAL CONDUIT IN 1ST FLOOR SERVER ROOM IN SURGERY CENTER.
12/14/2009 INSP - FULL RSPANGLE Approved 3.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN HALLWAY FO OLD O.R. 1ST FLOOR.
12/14/2009 INSP - FULL RSPANGLE Approved 2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN HALLWAY OUTSIDE OF DIRTY ROOM.
12/14/2009 INSP - FULL RSPANGLE Approved 1.) TFC 703.1.1 SEAL AROUND PIPING WHERE IT PENETRATES THE CEILING TILE IN 1ST FLOOR DIRTY ROOM.