Case: T09FR03762
Case Details
Entered Date:
12/14/2009
Applicant:
BROADWAY PARTNERS 128 LLC
Description:
Full inspection done 12/14/09; Paul Nagy - maint sup - 885-3590; R2 / B occupancy;
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03762
Case Description: INSPECTION
Total Completed Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2009 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Double keyed lock on door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolt from wood door in game room. [replace with "thumb turn" type] |
12/14/2009 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Poolside emergency phone: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ 911 Phone shall be maintained in a working order. |
12/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Open space in electrical panel: TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _____Place an approved "blank" in the space. |
12/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. |
12/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove or replace with approved fused power strip. |
12/14/2009 | INSP - FULL | BCOBB | Approved | Please correct the following Tucson Fire Code violations: |