Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

12/11/2009

Applicant:

ADVANCED CERAMICS RESEARCH INC

Description:

Full Inspection

Completed Inspections

Case Status: FIELD
Case Number: T09FR03740
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
12/11/2009 VIOL - MEANS OF EGRESS BCORRALE Approved ____Exit sign/Emergency lighting out. IFC2006 1011.5.3-Power Source ____All nonfunctioning lighting repair bulbs are on order at this time.
12/11/2009 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved ____Main control valve on sprinkler riser not secured. IFC2006 901.6-Testing and Maintanence ____Secure main control valve with chain and lock.
12/11/2009 INSP - FULL BCORRALE Approved On 12/10/09, a fire inspection was conducted at BAE systems, 3292 E. Hemispere Lp. Please correct the following Tucson Fire Code violations. All code references are from the 2006 International Fire Code, with local modifications.