Case: T09FR03709
Case Details
Entered Date:
12/09/2009
Applicant:
ARNESON RANCH INC
Description:
Buffalo Wild Wings 5yr. check valve.12/9/09
Outstanding Inspections
Case Number: T09FR03709
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained. 5yr. Internal valve inspection Appendix C102.11.1 Inspection Check Valves shall be internally inspected every five years to verify that all components operate properly and are in good condition. _____Have internal valve inspection and gauges done. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03709
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2009 | COMPL - REINSPECTION | MPursley | Approved | All corrections made 12/9/09. |