Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/09/2009

Applicant:

KIVA-STAR PARTNERS LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03705
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
12/09/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Service and tag all extinguishers.
12/09/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Complete smoke detector log included and provide during reinspection.
12/09/2009 VIOL - FIRE RESIST.RATED CONST JVINCENT Approved 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained. ____Repair drywall in Chapter room. Hole in ceiling.
12/09/2009 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Approved 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ____Coverplate needed ceiling fan outlet. Exposed electrical. Chapter room.
12/09/2009 INSP - FULL JVINCENT Approved FULL FIRE INSPECTION.