Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/07/2009

Applicant:

170 N HARRISON LLC

Description:

Tucson Pool & Spa initial inspection 12/7/09

Outstanding Inspections

Case Number: T09FR03699
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/07/2009 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Non required fire protection systems and equipment shall be inspected, tested and maintained or removed.
12/07/2009 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. _____Remove drop bar from side door. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the side egress door, as bolt lock of any kind are not permitted 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03699
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/22/2009 INSP - REINSPECTION MPursley Approved Some corrections made, next reinspection due 1/4/10.