Description:

Full Fire Prevention Inspection. Ira Waluyo 292-5988

Outstanding Inspections

Case Number: T09FR03695
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/07/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. The open space in the electrical panel located in the kitchen by the ice machine shall be covered.
12/07/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the kitchen hood extinguishing system and correct any deficiencies noted on the inspection report. _____1. Service and tag the automatic sprinkler system. NOTE: Provide documentation.
12/07/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the south EXIT door located in the kitchen and replace it with a thumb-turn lock.
12/07/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair the emergency lighting bulbs located on the EXIT sign located in the kitchen. _____2. Repair or replace the EXIT sign and emergency lighting bulbs located above the north entrance door.
12/07/2009 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Secure the CO2 cylinder located in the east soda station room with a chain or strap to prevent falling. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03695
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/07/2009 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code violations.