Case: T09FR03686
Case Details
Entered Date:
12/03/2009
Applicant:
FOOTHILLS BUSINESS VENTURES LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR03686
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2009 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | IFC 901.4.1 Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. ___1. NEED TO HAVE SPRINKLER SYSTEM TESTED OR SHOW REPORT THAT ITS BEEN DONE REPAIR ANY DEFECIENCIES. Re-inspection date scheduled on or after December 17th, 2009. If you have any questions or concerns please call Inspector Motto at 837-7127. Thank you, _____________________________________________ William Motto, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________Date:__________ Captain - Tucson Fire Dept. ________________________________________ |
| 12/03/2009 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ___1. NEED TO REPAIR EXIT LIGHT AT THE NORTH EXIT. |
| 12/03/2009 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: ___1. REPAIR EMERGENCY POWER LIGHT OVER TABLE 28. ___2. REPAIR EMERGENCY POWER LIGHT UPSTAIRS NORTH EXIT. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03686
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2009 | INSP - FULL | WMOTTO | Approved | UPON REINSPECT ALL VIOLATIONS FIXED. |