FIRE SPRINKLER SYSTEM INSPECTION

Outstanding Inspections

Case Number: T09FR03682
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/02/2009 VIOL - FIRE PROTECTION SYSTEMS RHEATH Correction Required Incomplete sprinkler coverage in the kitchen area; behind the serving line and in the 2 walk-in freezers. Install additional sprinklers to provide required coverage. IFC 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.