Case: T09FR03679
Case Details
Entered Date:
12/02/2009
Applicant:
BROADWAY POWER CENTER GROUP LLC
Description:
Dolce Vita initial inspection 12/1/09
Outstanding Inspections
Case Number: T09FR03679
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2010 | VIOL - PRECAUTION AGAINST FIRE | MPURSLEY | Correction Required | 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep hot water heater clean(excessive soot build up). |
01/08/2010 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-keyed lock and replace with an approved locking device such as, thumb turn lock or panic hardware 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03679
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2010 | INSP - REINSPECTION | MPursley | Approved | All corrections made 1/20/10. |