Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/30/2009

Applicant:

CAMELBACK CORPORATE CENTER

Description:

FULL FIRE INSPECTION. CONTACT: DANIEL SARNI@ 325-7766

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03667
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/30/2009 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____1. NEED TO HAVE HOOD SYSTEM SERVICED. PROVIDE A REPORT UPON REINSPECTION. ____2. NOZZLES NEED TO BE ADJUSTED ON HOOD SYSTEM FOR PROPER COVERAGE. Re-inspection date scheduled on or after December 14th, 2009. If you have any questions or concerns please call Inspector motto at 837-7127. Thank you, _____________________________________________ William Motto, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________Date:__________ Captain - Tucson Fire Dept. ________________________________________
12/01/2009 INSP - FULL WMOTTO Approved