Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/30/2009

Applicant:

SUNBELT STORES CO LTD PRTNRSHP

Description:

Full Fire Inspection. Lyon Hassing 514-7004

Outstanding Inspections

Case Number: T09FR03663
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
11/30/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Provide the Automatic Sprinkler System inspection report for fire department records. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
11/30/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.4 Power source. Where emergency illumination is required in Section 1027.5, exit signs shall be visible under emergency illumination conditions. _____1. The EXIT sign located in the kitchen shall have emergency back-up power.
11/30/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the broken emergency lighting unit located in the dinning area on the east wall. _____2. Repair or replace the broken emergency lighting unit located in the dinning area on the west wall. _____3. Repair or replace the broken emergency lighting unit located in the men's restroom. _____4. Repair or replace the broken emergency lighting unit located in the dinning area on the west wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03663
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/17/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.