Case: T09FR03631
Case Details
Entered Date:
11/23/2009
Applicant:
DAVE GRABBERT RANCH INC
Description:
Posh Paws initial inspection 11/20/09
Outstanding Inspections
Case Number: T09FR03631
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2009 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03631
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2009 | INSP - REINSPECTION | MPursley | Approved | The occupant load is <50 so the emergency light was removed by occupant 12/21/09. |