Description:

Full inspection done 11/13/09; "B" occupancy ; Donna Weilburg / Yvette Villamana- owner / manager; 751-4556.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03581
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
11/17/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Sprinkler system: sprinkler head box needs wrench: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. ______ Replace wrench in box. Re-inspection date scheduled on or after December 1st, 2009. If you have any questions or concerns please call Inspector Cobb at 837-7106. Thank you,
11/17/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. Re-inspection date scheduled on or after December 1st, 2009. If you have any questions or concerns please call Inspector Cobb at 837-7106.
11/17/2009 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code violations: