Case: T09FR03581
Case Details
Entered Date:
11/17/2009
Applicant:
ODIE ENTERPRISES LLC
Description:
Full inspection done 11/13/09; "B" occupancy ; Donna Weilburg / Yvette Villamana- owner / manager; 751-4556.
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03581
Case Description: INSPECTION
Total Completed Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2009 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Sprinkler system: sprinkler head box needs wrench: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. ______ Replace wrench in box. Re-inspection date scheduled on or after December 1st, 2009. If you have any questions or concerns please call Inspector Cobb at 837-7106. Thank you, |
| 11/17/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. Re-inspection date scheduled on or after December 1st, 2009. If you have any questions or concerns please call Inspector Cobb at 837-7106. |
| 11/17/2009 | INSP - FULL | BCOBB | Approved | Please correct the following Tucson Fire Code violations: |