Case: T09FR03460
Case Details
Entered Date:
11/04/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection Building Rep: Marina Crane Phone #
Outstanding Inspections
Case Number: T09FR03460
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
11/04/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels and equipment according to code. |