Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR03422
Case Details
Entered Date:
11/02/2009
Applicant:
CAMPUS-STAR PASS LLC
Description:
Call out for Fire Alarm and Sprinkler system out of service.
Outstanding Inspections
Case Number: T09FR03422
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Replace the broken sprinkler head and return the sprinkler system back into service. _____2. Repair the fire alarm system and place it back in service. Fire watch shall be established until both systems are back in service. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03422
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2009 | INSP - LIFE SAFETY | JBURGE | Approved | Both sprinkler and fire alarm systems were place back in servce on 10/31/2009 at 1900 hrs. |
| 11/02/2009 | INSP - LIFE SAFETY | JBURGE | Approved | Call out from EN-1 for a sprinkler and fire alarm system out of service. |