Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

11/02/2009

Applicant:

CAMPUS-STAR PASS LLC

Description:

Call out for Fire Alarm and Sprinkler system out of service.

Outstanding Inspections

Case Number: T09FR03422
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
11/02/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Replace the broken sprinkler head and return the sprinkler system back into service. _____2. Repair the fire alarm system and place it back in service. Fire watch shall be established until both systems are back in service.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03422
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
End Date Description Inspector Results Comments
11/02/2009 INSP - LIFE SAFETY JBURGE Approved Both sprinkler and fire alarm systems were place back in servce on 10/31/2009 at 1900 hrs.
11/02/2009 INSP - LIFE SAFETY JBURGE Approved Call out from EN-1 for a sprinkler and fire alarm system out of service.