Case: T09FR03398
Case Details
Entered Date:
10/28/2009
Applicant:
BETA EPSILON OF ALPHA PHI BLDG CO
Description:
FULL FIRE INSPECTION.
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03398
Case Description: INSPECTION
Total Completed Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2009 | VIOL - MEANS OF EGRESS | WMOTTO | Approved | 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. ____Always keep exit door in chapter room clear of obstructions. |
| 10/28/2009 | VIOL - MEANS OF EGRESS | WMOTTO | Approved | 1027.5 Illumination emergency power. ____repair exit sign/lighting unit in sleeping porch. |
| 10/28/2009 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Approved | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Service and tag all extinguishers. All due for annual inspection. |
| 10/28/2009 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Approved | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____fire alarm annual inspection due. Provide a copy of report. |
| 10/28/2009 | VIOL - INT.FINISH, DEC. MATL'S | WMOTTO | Approved | 807.1 General requirements. In occupancies in Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible. ____The hanging of black plastic on walls and ceilings shall be prohibited. |
| 10/28/2009 | VIOL - ADMINISTRATION | WMOTTO | Approved | 107.2.1 Test and inspection records. Required test and inspection records shall be available to the fire code official at all times or such records as the fire code official designates shall be filed with the fire code official. ____provide a copy of annual fire sprinkler inspection report. |
| 10/28/2009 | INSP - FULL | WMOTTO | Approved | FULL FIRE INSPECTION. |