Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/28/2009

Applicant:

BETA EPSILON OF ALPHA PHI BLDG CO

Description:

FULL FIRE INSPECTION.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03398
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
10/28/2009 VIOL - MEANS OF EGRESS WMOTTO Approved 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. ____Always keep exit door in chapter room clear of obstructions.
10/28/2009 VIOL - MEANS OF EGRESS WMOTTO Approved 1027.5 Illumination emergency power. ____repair exit sign/lighting unit in sleeping porch.
10/28/2009 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Approved 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Service and tag all extinguishers. All due for annual inspection.
10/28/2009 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____fire alarm annual inspection due. Provide a copy of report.
10/28/2009 VIOL - INT.FINISH, DEC. MATL'S WMOTTO Approved 807.1 General requirements. In occupancies in Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible. ____The hanging of black plastic on walls and ceilings shall be prohibited.
10/28/2009 VIOL - ADMINISTRATION WMOTTO Approved 107.2.1 Test and inspection records. Required test and inspection records shall be available to the fire code official at all times or such records as the fire code official designates shall be filed with the fire code official. ____provide a copy of annual fire sprinkler inspection report.
10/28/2009 INSP - FULL WMOTTO Approved FULL FIRE INSPECTION.