Case: T09FR03316
Case Details
Entered Date:
10/20/2009
Applicant:
QUIK MART STORES INC
Description:
Full Inspection 10/20/09
Outstanding Inspections
Case Number: T09FR03316
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the drop bar and replace with an approved locking device such as, thumb turn lock or panic hardware 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03316
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2009 | COMPL - REINSPECTION | MPursley | Approved | All corrections made 11/3/09. |