Case: T09FR03293
Case Details
Entered Date:
10/19/2009
Applicant:
DIAZ LUCILA G & DIAZ-SMITH MARTHA &
Description:
Full Fire Prevention Inspection. Juan Suazo 623-2222
Outstanding Inspections
Case Number: T09FR03293
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace all missing electrical outlet covers located in the North room. |
| 10/19/2009 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. _____1. Replace all missing ceiling tiles located in the North room. |
| 10/19/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the hood extinguishing system. _____2. Service and tag all portable fire extinguishers. _____3. Align the hood extinguishing system nozzles to properly cover the cooking equipment. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 10/19/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.3.5 Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles. _____1. Remove both security grills from the doors located in the North room. |
| 10/19/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove all double-keyed locks from the North room doors. NOTE: Only one thumb-turn lock is permitted on each door. |
| 10/19/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. _____1. Post the above wording on the inside of the entrance security grill. |
| 10/19/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove all slide bolts from the North room doors. |
| 10/19/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located on the West wall in the dinning area. |
| 10/19/2009 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Secure all compressed gas cylinders located in the kitchen to prevent falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03293
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |