Case: T09FR03271
Case Details
Entered Date:
10/14/2009
Applicant:
MATZ ENTERPRISES INC
Description:
Best Buy Furniture fire inspection.
Outstanding Inspections
Case Number: T09FR03271
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2009 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
| 10/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
| 10/14/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03271
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 10/29/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |