Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/14/2009

Applicant:

CAROLINA LEASING LIMITED PRTNRSHP 80% &

Description:

Full Fire Prevention Inspection. Gary Geisler 296-3330

Outstanding Inspections

Case Number: T09FR03264
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/14/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1. Post the above wording on the inside of the entrance doors.
10/14/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove the slide bolts from all exterior doors in the building. NOTE: Only one thumb-turn lock is allowed on the doors. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
10/14/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. All exit signs located in the building shall be internally illuminated at all times.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03264
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/28/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.