Case: T09FR03259
Case Details
Entered Date:
10/13/2009
Applicant:
CITY OF TUCSON
Description:
FULL MAITS / FIRE CODE COMPLIANCE INSPECTION
Outstanding Inspections
Case Number: T09FR03259
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2009 | INSP - FULL | RHEATH | Scheduled | The MAITS team conducted a FULL COMPLIANCE inspection. Discrepancies noted must be repaired by the 11/09/2009 suspense. R. HEATH, INSPECTOR ____________________ M. JONES, FIRE CAPTAIN_____________________ |
10/13/2009 | VIOL - BUILDING SVCS & SYSTEMS | RHEATH | Correction Required | Door 118: the GFCI did not trip when tested. Replace GFCI. NFPA Standard 70. |
10/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | RHEATH | Correction Required | Brake Lathe Room: The fire extinguisher is not securly mounted. Mount extinguisher as shown. IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or rackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. |
10/13/2009 | VIOL - MEANS OF EGRESS | RHEATH | Correction Required | In the event of power supply failure, an emergency electrical system shall automatically illuminate the exit components. |