Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/12/2009

Applicant:

BROADWAY/CAMINO SECO LLC

Description:

Initial inspection 10/9/09

Outstanding Inspections

Case Number: T09FR03243
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/12/2009 VIOL - PRECAUTION AGAINST FIRE MPURSLEY Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
10/12/2009 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____Place appropriate address numbers on front of building.
10/12/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained, have sprinkler system inspected.
10/12/2009 VIOL - COMPRESSED GASES MPURSLEY Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03243
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/09/2009 INSP - REINSPECTION MPursley Approved Still hasn't had sprinklers inspected;I gave them a pre-cite on 12/9/09 with a reinspection due 12-23-09.