Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/12/2009

Applicant:

FLORES PABLO C & FLORES ANNA CONSUELO JT/RS

Description:

Chato's towing fire inspection.

Outstanding Inspections

Case Number: T09FR03239
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
10/12/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 304.2 - Storage. Storage of combustible rubbish shall not produce conditions that will create a nuisance or a hazard to the public health, safety or welfare.
10/12/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
10/12/2009 VIOL - MOTOR FUEL DISPENSING JLOYA Violation 2211.2.1 Cleaning of parts. Cleaning of parts shall be conducted in listed and approved parts-cleaning machines.
10/13/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
10/13/2009 VIOL - HAZARDOUS MATERIALS,GEN JLOYA Violation 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere. ___Clean oil spills in back.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03239
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/12/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346. Received by_________________ Date__________
10/29/2009 INSP - REINSPECTION JLOYA Approved All violations abated.