Entered Date:

10/05/2009

Applicant:

TUCSON ST MARY'S PLAZA LLC

Description:

Full Fire Prevention Inspection. Jerry Benitez 624-8442

Outstanding Inspections

Case Number: T09FR03178
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/05/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____1. Remove all storage from obstructing the sprinkler system riser and control valves.
10/05/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Replace the missing Fire Department Connection caps loacted on the North side of the building. _____2. Service and test the emergency generator or provide documentation of the annual inspection.
10/05/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Remove all grease accumulation from the kitchen hood systems. NOTE: Provide documentation of the cleanings. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
10/05/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The EXIT sign located above the Southeast exit door shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03178
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/28/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.