Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR03149
Case Details
Entered Date:
10/02/2009
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Full Fire Prevention Inspection Building Rep: Chris Brin Phone # 792-4338
Outstanding Inspections
Case Number: T09FR03149
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
10/02/2009 | VIOL - FIRE RESIST.RATED CONST | JLONGO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
10/02/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo) |