Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/01/2009

Applicant:

SMITH FAMILY REAL ESTATE INVESTORS LTD

Description:

Initial inspection 9/30/09

Outstanding Inspections

Case Number: T09FR03123
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/01/2009 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____Have ladder removed from riser room.
10/01/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical outlets.
10/01/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards
10/01/2009 VIOL - COMPRESSED GASES MPURSLEY Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03123
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/19/2009 INSP - REINSPECTION MPursley Approved All corrections made 11/19/09