Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR03099
Case Details
Entered Date:
09/22/2009
Applicant:
TUCSON SPEEDWAY SQUARE LLC
Description:
Full Fire Prevention Inspection
Outstanding Inspections
Case Number: T09FR03099
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 09/22/2009 | VIOL - BUILDING SVCS & SYSTEMS | DSIWARSKI | Violation | IFC.605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ____Extension cords shall not be substituted for permanent wiring in various locations in building. |
| 09/22/2009 | VIOL - BUILDING SVCS & SYSTEMS | DSIWARSKI | Violation | IFC.605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ____Electrical cover plates required by refrigerator and front door. |
| 09/22/2009 | VIOL - FIRE PROTECTION SYSTEMS | DSIWARSKI | Violation | IFC.906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Portable fire extinguishers must be serviced and mounted. |
| 09/22/2009 | VIOL - MEANS OF EGRESS | DSIWARSKI | Violation | IFC.1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,,, ____Sign required on front door. |