Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/22/2009

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full Fire Prevention Inspection. Zoraya Sandoval 620-1720

Outstanding Inspections

Case Number: T09FR03086
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/22/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Remove all grease accumulation from the hood system.
09/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located in the kitchen.
09/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove the storage from obstructing the exit door located in the kitchen.
09/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. Both North exit signs shall be fully illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03086
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/13/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.