Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/22/2009

Applicant:

6TH & 6TH HOLDING CO LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03078
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
09/22/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2006 IFC 703.1 NEED TO BLOCK OFF IN THE CEILILNG WHERE3 THE DRYWALL ENDS. AS THE CEILING IS NOW, A FIRE CAN GET INTO THE ATTIC AS THERE IS NO FIRE BLOCKAGE.
09/22/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 SERVICE AND TAG FIRE EXTINGUISHER BY KILNS
09/22/2009 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC605.5 IN RETAIL TILE STORE, REMOVE THE 2 EXTENSION CORDS USED TO POWER THE LIGHTS. REMOVE EXTENSION CORD BY KILNS WHICH POWERS THE LIGHT IN CEILING
02/05/2010 INSP - FULL WMOTTO Approved UPON REINSPECTION ALL VIOLATIONS ABATED