Case: T09FR03068
Case Details
Entered Date:
09/21/2009
Applicant:
ORACLE INNKEEPER LLC
Description:
Full Fire Prevention Inspection Building Rep: Nick Morey Phone # 869-9651
Outstanding Inspections
Case Number: T09FR03068
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
| 09/21/2009 | VIOL - FIRE SERVICE FEATURES | JLONGO | Correction Required | 503.6 Security gates. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. ______ Fix your access gate for emergency and Fire department use. 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. ______ A Lock box and keys shall be placed on the outside of your main building for fire department access. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ |