Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

09/21/2009

Applicant:

6TH & 6TH HOLDING CO LLC

Description:

Bldg. Insp. prior to occupying

Outstanding Inspections

Case Number: T09FR03063
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
09/21/2009 VIOL - BUILDING SVCS & SYSTEMS GDAURIA Correction Required TFC 605 - Install GFI protection for the 2 outlets adjacent to (w/in 48") of sink. TFC 605 - Install blanks in breaker box to prevent shock
09/21/2009 VIOL - FIRE RESIST.RATED CONST GDAURIA Correction Required TFC 703 - seal ceiling penetration @ electrical penetrations in bath area
09/21/2009 VIOL - MEANS OF EGRESS GDAURIA Correction Required TFC 1011 - Repair exit sign illumination (2)