Case: T09FR03063
Case Details
Entered Date:
09/21/2009
Applicant:
6TH & 6TH HOLDING CO LLC
Description:
Bldg. Insp. prior to occupying
Outstanding Inspections
Case Number: T09FR03063
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
09/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | GDAURIA | Correction Required | TFC 605 - Install GFI protection for the 2 outlets adjacent to (w/in 48") of sink. TFC 605 - Install blanks in breaker box to prevent shock |
09/21/2009 | VIOL - FIRE RESIST.RATED CONST | GDAURIA | Correction Required | TFC 703 - seal ceiling penetration @ electrical penetrations in bath area |
09/21/2009 | VIOL - MEANS OF EGRESS | GDAURIA | Correction Required | TFC 1011 - Repair exit sign illumination (2) |