Case: T09FR03040
Case Details
Entered Date:
09/17/2009
Applicant:
USRP FUNDING 2001-A LP
Description:
Full Fire Prevention Inspection.
Outstanding Inspections
Case Number: T09FR03040
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3- Cleaning. 1. Provide documentation of the most current hood system cleaning. |
09/17/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.3- Exit sign illumination. 1. The exit sign located in the outside dinning area shall be internally illuminated at all times. |
09/17/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.8- Panic Hardware. 1. Remove the thumb-turn lock from the north door in the kitchen or remove the panic hardware. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03040
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |