Type:

INSPECTION

Entered Date:

09/17/2009

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire prevention inspection.

Outstanding Inspections

Case Number: T09FR03037
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
09/17/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6- Inspection, testing and maintenance. 1. Service and tag the hood extinguishing systems.
09/17/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.3- Cleaning. 1. Provide documentation of the hood system cleaning.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03037
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/06/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.