Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/17/2009

Applicant:

LYNX ASSOC LP DBA LYNX ASSOC LTD PRTN

Description:

Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T09FR03036
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/17/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1- Maintenance. 1. Replace the damaged ceiling tile located near the buffet line.
09/17/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6- Inspection, testing and maintenance. 1. Service and test the fire alarm system. NOTE: Provide documentation.
09/17/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5- Illumination emergency power. 1. Repair or replace all emergency lighting units that do not work.
09/17/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.8- Panic hardware. 1. Remove the double-keyed lock from the panic hardware door located by the managers office.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03036
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/06/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.