Case: T09FR03036
Case Details
Entered Date:
09/17/2009
Applicant:
LYNX ASSOC LP DBA LYNX ASSOC LTD PRTN
Description:
Full Fire Prevention Inspection.
Outstanding Inspections
Case Number: T09FR03036
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2009 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | IFC 703.1- Maintenance. 1. Replace the damaged ceiling tile located near the buffet line. |
09/17/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6- Inspection, testing and maintenance. 1. Service and test the fire alarm system. NOTE: Provide documentation. |
09/17/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5- Illumination emergency power. 1. Repair or replace all emergency lighting units that do not work. |
09/17/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.8- Panic hardware. 1. Remove the double-keyed lock from the panic hardware door located by the managers office. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03036
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |