Case: T09FR02949
Case Details
Entered Date:
09/11/2009
Applicant:
HEIGHTS PROPERTIES LLP
Description:
Full Fire Prevention Inspection
Outstanding Inspections
Case Number: T09FR02949
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The light fixture located on the ceiling of the water heater closet shall be repaired. |
09/11/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 The multiplug adapter located at the dining room for teh fans is prohibited and shall not be used. Power strips with overcurrent protection may be used in place of the multiplug adapter. |
09/11/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Blanks shall be installed to replace or cover holes left from missing breaker switches in the electrical panel located in the water heater closet. |
09/11/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.6 The portable fire extinguisher and manual pull station for the hood system shall not be blocked by storage. |
09/11/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 The portable fire extinguisher located near the dishwashing station shall be mounted on a hanger or bracket. |
09/11/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 The emergency light fixture located at the east end of the kitchen shall be repaired. |
09/11/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 The emergency light located on the ceiling near the dishwashing station shall be repaired. |
09/11/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.4 The exit sign located at the southwest exit shall be repaired so that it remains lit. |
09/11/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.5 Curtains shall not be placed over the exit door located on the west side of the dining area. |
09/11/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.8 The keyed lock located on the west dining room exit shall be removed. Panic hardware is the only allowable locking device on this door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02949
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2009 | INSP - FULL | TKNAPP | Approved |