Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR02949
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
09/11/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The light fixture located on the ceiling of the water heater closet shall be repaired.
09/11/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 The multiplug adapter located at the dining room for teh fans is prohibited and shall not be used. Power strips with overcurrent protection may be used in place of the multiplug adapter.
09/11/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Blanks shall be installed to replace or cover holes left from missing breaker switches in the electrical panel located in the water heater closet.
09/11/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.6 The portable fire extinguisher and manual pull station for the hood system shall not be blocked by storage.
09/11/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 The portable fire extinguisher located near the dishwashing station shall be mounted on a hanger or bracket.
09/11/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 The emergency light fixture located at the east end of the kitchen shall be repaired.
09/11/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 The emergency light located on the ceiling near the dishwashing station shall be repaired.
09/11/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.4 The exit sign located at the southwest exit shall be repaired so that it remains lit.
09/11/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.5 Curtains shall not be placed over the exit door located on the west side of the dining area.
09/11/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.8 The keyed lock located on the west dining room exit shall be removed. Panic hardware is the only allowable locking device on this door.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02949
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/30/2009 INSP - FULL TKNAPP Approved