Description:

Inspection

Outstanding Inspections

Case Number: T09FR02941
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
09/10/2009 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 Combustible materials shall not be stored in the water heater closet.
09/10/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 603.6 The water heater shall be maintained so as to not create a fire hazard. This unit seems to be not venting properly. Heater shall be serviced by a licensed contractor and proof of this service shall be provided.
09/10/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.7 A steel baffel shall be installed between the fryer and the open flames of the adjacent cooking appliance in the kitchen.
09/10/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A readily visible sign shall be posted at the south main exit stating "This door to remain unlocked when building is occupied".
09/10/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 The emergency illumination light located at the dining area shall be repaired.
09/10/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.4 The exit sign located at the south main exit shall be repaired.
09/10/2009 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.5.3 The compressed gas cylinder (CO2) located in the stockroom shall be secured to prevent it from falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02941
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/19/2009 INSP - FULL TKNAPP Approved