Case: T09FR02939
Case Details
Entered Date:
09/10/2009
Applicant:
2005 PARTNERSHIP
Description:
Full Fire Prevention Inspection. Chuck Ohswaldt 629-0820
Outstanding Inspections
Case Number: T09FR02939
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. The north sprinkler shop door shall not be welded shut and shall be repaired for normal operation. _____2. Remove all double-keyed locks from all office doors. NOTE: Replace the double-keyed locks with thumb turn locks. |
| 09/10/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. _____1. Post the above wording on the inside of the main entrance door. |
| 09/10/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove the storage rack from obstructing the north door in the HVAC shop. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 09/10/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the deadbolts from all panic hardware doors. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02939
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |