Case Number: T09FR02847
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
09/03/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open wiring connections and disconnected conduit located at the dishwasher shall be repaired.
09/03/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6 The grease filter located at the south hood shall be repaired or replaced.
09/03/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.2/1008.1.8/1008.1.8.4 The means of egress from the north kitchen exit to the public way shall be readily openable without the use of a key or special knowledge or effort. The magnetic lock on the chain link gate shall be removed. The manually operated surface bolt lock on the north yard's metal gate is not permitted and shall be removed. Padlocks shall not be used on either of these gates.
09/03/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 An exit sign shall be installed at the east side take out exit door. The sign shall be internally or exturnally illuminated at all times.
09/03/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 The emergency lighting fixtures located at 1) The main south exit, 2) west wall of dining area, 3) southeast exit, shall be repaired.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02847
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/20/2009 INSP - FULL TKNAPP Approved