Description:

China Olive fire inspection.

Outstanding Inspections

Case Number: T09FR02813
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
09/01/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
09/01/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
09/01/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
09/01/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
09/01/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. ___ Replace pin at pull station. ___ Reduce number of appliances under hood or increase number of detectors. ___ Install quick seal at all hood penetrations.
09/01/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
09/01/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02813
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/01/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
10/05/2009 INSP - REINSPECTION JLOYA Approved All violations abated.