Case: T09FR02775
Case Details
Entered Date:
08/27/2009
Applicant:
NORTH CROWN INVESTMENT CO LTD PRTNRSHP
Description:
Full Fire Prevention Inspection
Outstanding Inspections
Case Number: T09FR02775
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 08/27/2009 | VIOL - FIRE PROTECTION SYSTEMS | DSIWARSKI | Violation | IFC.906.1 Two (2) protection caps are required on sprinkler connections. IFC.901.6 Sprinkler system (5) year check valve test is due. Annual sprinkler test is in compliance. |
| 08/27/2009 | VIOL - MEANS OF EGRESS | DSIWARSKI | Violation | IFC.1008.1.8.3 Five (5) doors in show room require signs:"This Door IS TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". |