Case: T09FR02762
Case Details
Entered Date:
08/26/2009
Applicant:
ELEFANTE VENTURE NO 1 LLC
Description:
Full inspection conducted 8/12/09 - generated by hood system deficiency report T09FR02557 I have received a copy of this report and understand the corrections needed: ________________ Business Representative: Suzanne Elefante, Phone: 790-4702 Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after)
Outstanding Inspections
Case Number: T09FR02762
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2009 | INSP - FULL | DGREENLE | Violation | Please correct the the following violations of the Tucson Fire Code: TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____ Remove extension cord connected to electrical service panel in kitchen _____ Exposed light socket, outside back door TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Behind Bar TV/Refrigerator _____ Center column - kitchen TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. * Plug power strip directly into wall outlet. _____ Office _____ Office _____ Kitchen/Freezer TFC 605.5 - Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords shall be used only with portable appliances. _____ Green extension cord over entry to behind bar. _____ Freezer storeroom TFC 605.6 - Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. _____ Replace grill covering electrical motor and contacts - kitchen freezer TFC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exceptions: In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. *Replace keyed deadbolt with thumb-turn type _____ Back door _____ Front Door TFC 3003.5 - Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement… ____ Secure compressed gas cylinders in kitchen TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. _____ Exit Sign/Emergency Light - Kitchen _____ Exit Sign - Dining Room Back door |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02762
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2009 | INSP - REINSPECTION | DGREENLE | Approved | some electrical done, still awaiting pull station re-location and e-light/exit sign repair among others |