Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/25/2009

Applicant:

ELITE PERFORMANCE LLC

Description:

Full 8/25/09 Reinspection due 9/8/09

Outstanding Inspections

Case Number: T09FR02756
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
08/25/2009 VIOL - BUILDING SVCS & SYSTEMS JVALDEZ Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips.
08/25/2009 VIOL - FIRE RESIST.RATED CONST JVALDEZ Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____ Fix and repair all openings or holes in the ceiling
08/25/2009 VIOL - MEANS OF EGRESS JVALDEZ Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the drop bar hardware and/or replace with an approved locking device such as, thumb turn lock or panic hardware
08/25/2009 VIOL - FLAMMABLE LIQUIDS JVALDEZ Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented.
10/09/2009 INSP - REINSPECTION MPURSLEY Correction Required All corrections made except emergency vent on tanks before business closed.