Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/25/2009

Applicant:

RAM-DUR ENTERPRISES INC

Description:

Manny's tire shop fire inspection.

Outstanding Inspections

Case Number: T09FR02752
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
08/25/2009 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.
08/25/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
08/25/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
08/25/2009 VIOL - TIRE REBUILDING/STORAGE JLOYA Violation 2505.4 Distance from lot lines and buildings. Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings. Exception #1: For existing storage before August 4, 2004 individual piles not exceeding 5,000 square feet (464.5m²) of continuous area shall be located 10 feet (3048.3 mm) from buildings and lot lines for storage not exceeding 6 feet (1829 mm) in height. Exception #2: For existing storage before August 4, 2004 individual piles exceeding 6 feet (1829 mm) in height shall be located 20 feet (6096.6 mm) from buildings and lot lines.
08/25/2009 VIOL - LIQUID PETROLEUM GASES JLOYA Violation 3803.2.1 Portable containers. Portable LP-gas containers, as defined in NFPA 58, shall not be used in buildings. Received by_________________ Date__________

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02752
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/25/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.