Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/25/2009

Applicant:

CIOLLI FRANK A

Description:

Full Fire Prevention Inspection Building Rep: Heiko Langrehr Phone # 884-7377 548-3795

Outstanding Inspections

Case Number: T09FR02749
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
08/25/2009 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
08/25/2009 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ place proper covers over the Electrical Panels. (Liquor room, back room) 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical outlets (up stairs bar) _____ Cover all loose wires and dead outlets. 605.4 Multi-plug adapters Multi-plug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited. _____ All Multi-plug adapters shall be removed or replace with approved fused power strips. (Register)
08/25/2009 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Maintain and always have all hood system filters in place while operational. _____ Service and tag your hood system. Show bids for your new system upgrade. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code. (Several through out) 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ The hood system in your building has been found unfit and requires a cleaning. You are to have your hood system cleaned immediately and provide the proper paper work to prove that the required cleaning has been done professionally.
08/25/2009 VIOL - MEANS OF EGRESS JLONGO Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, or replace the emergency lighting unit(s) in order to meet code standards (attached to exit signs, top floor bar) 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards. (Back North exit, Back East exit, Main exit, upper floor) 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed… Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). 3. No additional locks or latches shall be added _____ Remove your chain and pad lock from your outside patio panic hardware doors, and repair the broken panic hardware.
08/25/2009 VIOL - COMPRESSED GASES JLONGO Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times (Back kitchen) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)