Case: T09FR02738
Case Details
Entered Date:
08/24/2009
Applicant:
PALOMARK LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR02738
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2009 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 INSTALL BLANKS IN ELECTRICAL PANEL OUTLET PLATE NEEDED BY SNACK MACHINE |
| 08/24/2009 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.4 REMOVE MULTIPLUG ADAPTER IN NOE'S OFFICE AND REPLACE WITH A FUSED POWER STRIP |
| 08/24/2009 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SERVICE AND TAG FIRE EXTINGUSIHER IN KEY ROOM SERVICE AND TAG FIRE EXTINGUISHER BY WATER FOUNTAIN |
| 08/24/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.3 REPAIR THE 2 EXIT SIGNS INT HE TRUCK CENTER |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02738
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2009 | INSP - FULL | MWAINWRI | Approved |