Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/21/2009

Applicant:

HEIGHTS PROPERTIES LLP

Description:

Inspection

Outstanding Inspections

Case Number: T09FR02737
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/21/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cords shall not be used as a replacement for permanent wiring. The extention cord located at the workshop buffing table shall be removed.
08/21/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open wiring splice located on the buffer in the workshop is prohibited and shall be repaired. The buffer in the northeast corner of the table shall have its wiring secured and shall be grounded.
08/21/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The portable fire extinguishers (x3) located in the workshop area shall be inspected annually.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02737
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/04/2009 INSP - FULL TKNAPP Approved