Case: T09FR02737
Case Details
Entered Date:
08/21/2009
Applicant:
HEIGHTS PROPERTIES LLP
Description:
Inspection
Outstanding Inspections
Case Number: T09FR02737
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords shall not be used as a replacement for permanent wiring. The extention cord located at the workshop buffing table shall be removed. |
08/21/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open wiring splice located on the buffer in the workshop is prohibited and shall be repaired. The buffer in the northeast corner of the table shall have its wiring secured and shall be grounded. |
08/21/2009 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguishers (x3) located in the workshop area shall be inspected annually. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02737
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2009 | INSP - FULL | TKNAPP | Approved |