Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/19/2009

Applicant:

1031 HOLDER LLC

Description:

Full Fire Prevention Inspection. Brynda Welch 888-6970

Outstanding Inspections

Case Number: T09FR02717
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
08/19/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove all cube adapters and extension cords used for permanent wiring. NOTE: Replace them with fused multi-plug adapters.
08/19/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____1. Mount the portable fire extinguisher located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
08/19/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Rewmove the slide bolt from the west EXIT door.
08/19/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. _____1. Place the above wording on the inside of the the southeast exit door.
08/19/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. All exit signs shall be internally illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02717
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/22/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.